DC recorder backup

Executed energy and transfer study for a declared 24 V reference load. Hardware has not been built.

Result

The combined-derating case supplies the load for 134.09 s, against a 125 s recording and shutdown target. The nominal model runs for 343.56 s.

With a 2 ms interruption, the minimum modeled output is 23.707 V. The reference recorder minimum is 21.6 V.

The converter regulates 24 V output until its input reaches UVLO; these curves show its input side.
The converter regulates 24 V output until its input reaches UVLO; these curves show its input side.

Reference design

Load: 12 W for the first 2 s, then 6 W. Target: 120 s recording plus 5 s shutdown. The model keeps the 6 W load running after the target to measure margin.

Ten 100 F cells in series give 10 F nominal. Combined capacitance factors of 0.8 × 0.8 × 0.9 give 5.76 F. ESR rises from 0.12 to 0.36 ohm, charge starts at 21.6 V and efficiency falls to 82%. These are assumed design corners, not manufacturer ratings.

Functional power path. Component selection and detailed protection remain hardware work.
Functional power path. Component selection and detailed protection remain hardware work.

Calculation and checks

The model solves P = (Vcap − I × ESR) × I and dVcap/dt = −I/C. Load, converter and ESR energy are accumulated independently and checked against the decrease in ½CV². The two load intervals are integrated separately.

All 16 automated tests pass. They include the zero-ESR analytical solution, energy balance, integration refinement, current-limit cutoff, an undersized failing design and transfer-capacitor sensitivity.

caseruntime_smargin_to_125_smeets_reference_targetideal_upper_bound_sload_energy_jconverter_loss_jesr_loss_jenergy_residual_jcutoff
Nominal343.55981218.55981True345.75662073.35887240.686.645854.547473508864641e-12input UVLO
Capacitance tolerance274.44851149.44851True276.207071658.69107192.532465.32423-2.0463630789890885e-12input UVLO
Aged capacitance219.1594794.15947True220.567451326.95682154.014434.266961.1596057447604835e-11input UVLO
Cold and aged ESR339.17105214.17105True345.75662047.02631237.622519.729617.275957614183426e-12input UVLO
90% initial charge261.97281136.97281True264.04431583.83687183.841065.806793.865352482534945e-12input UVLO
Combined derating134.092259.09225True137.67913816.55352183.2662210.93542-9.094947017729282e-13input UVLO
Undersized 20 F cells25.20505-99.79495False25.94236163.2303236.58722.333522.3860849296397646e-08input UVLO

Transfer interruption

4700 µF output capacitor, derated to 3760 µF, with 50 mΩ ESR. Constant 12 W load.
4700 µF output capacitor, derated to 3760 µF, with 50 mΩ ESR. Constant 12 W load.

Storage comparison

storagedeliverable_energy_to_cutoff_whrequired_load_whbasis
10 x 100 F series bank, nominal0.57593301825627890.21166666666666667Integrated ESR and converter model; 24 to 10.5 V input window
10 x 100 F series bank, combined derating0.226820423168995920.211666666666666675.76 F, 0.36 ohm, 21.6 V initial, 82% conversion
Generic 19.2 V / 1 Ah battery reference7.311360.21166666666666667Energy estimate only; no discharge curve, peak current or BMS behavior modeled

The battery row is an energy-only comparison. Its load current capability, discharge curve, protection, charging and life-cycle behavior have not been modeled. It is not a selected or approved battery pack.

Component criteria

itemquantitycriterionreason
Storage cells10100 F nominal, 2.7 V rated each; qualify C >=57.6 F and ESR <=36 milliohm per cell at the declared combined cornerSeries equivalent 5.76 F and 0.36 ohm; 24 V maximum bank charge; cell imbalance still requires monitoring
Cell balancing / voltage supervision1Monitor and balance all 10 cells; prevent any cell exceeding its qualified voltage/temperature envelopeBank voltage alone cannot detect cell overvoltage; the virtual bench evaluates declared imbalance and ideal balancing cases
Current-limited charger124 V regulated bank endpoint; limit charge current and monitor temperature; isolate input on source lossThe virtual bench calculates ideal constant-current charging; real inrush and selected-part behavior remain model boundaries
Backup DC/DC stage1Regulated 24 V output, >=12 W peak, 10.5 to 24 V input, >=82% at worst corner, 2 A input capabilityEfficiency and UVLO assumptions must be checked on selected parts across load and temperature
Power-path isolation2Reverse-blocking paths on main supply and backup output; voltage/current ratings after transient measurementModel assumes ideal reverse isolation; no measured backfeed result
Output hold-up capacitor14700 microfarad nominal, >=3760 microfarad minimum, <=50 milliohm ESR; >=35 V voltage rating subject to transient qualificationSupports assumed 2 ms source transfer at 12 W
Protection and shutdown1Fuse/current limit sized against chosen conductors, short-circuit behavior and stored energy; recorder power-fail signal and verified shutdown acknowledgmentElectrical continuity cannot prove file-system integrity

Limits and next hardware checks

bench_acceptance.md records the unexecuted bench checks. Read results/summary.json, test-log.txt and verification.json for the executed evidence.

Source and reproduction

Method reference: Analog Devices, Energy Storage Using Supercapacitors. It informs loss and degradation treatment; numerical inputs here are separately declared assumptions.

python -m pip install -r requirements.txt
python run.py
python -m unittest -v

Virtual validation

Executed synthetic and theoretical run-through. The report includes cases, acceptance results and model boundaries.